Tonaquint Data Center
SAS70 Certified Audit
Design Features

DESIGN FEATURES

Colocation and Disaster Recovery Facility

SAS 70 Certified

Why TDC?

The Tonaquint Data Center was specifically designed for colocation and disaster recovery solutions. TDC design features provide an efficient and scalable building for customers to manage their growth.

Facility Size
Approximately 28,000 square feet.
Completed
3rd Quarter, 2008
Raised Floor Area
Raised floor area is 17,200 usable square feet
Floor Load
Typical structural capacity of 450 pounds per square foot.
Building Access
24x7x365
Building Security
Security system - State of the art system:
24x7x365
Video surveillance at all building entrances
Shipping and receiving dock with remote monitored gate and secured storage
Private parking area for all employees and customers
Monitored visitor parking
Telecommunications
Carriers currently installed:
360 Networks
UTOPIA
Tonaquint
Qwest
Interlinx
South Central
Level(3) Communications
Commercial Power
Utility - City Power
Most Economical Power in the region
25 MW primary substation
15 MW secondary substation
Delivers power capacity up to 225 w/sf
Total power plant 4 MW
Fuel Tank
Fuel storage for minimum 48-hr run time
Currently, 6,000+ gallons on site
Generators
Three (3) 2MW Caterpillar generators and eight (8) 750KVA Liebert UPS units
Entire generator plant designed at N+1 redundancy
Fire Supression
VESDA (Very Early Smoke Detection Alarm) above and below floor
Double interlock pre-action throughout
HVAC
DX30 ton computer room air conditioner units
N+1 redundancy on all systems
Ceiling Heights
Typically finished 10 feet from raised floor
Loading Area
Secure enclosed loading area